Permit Number - T09CM03069
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/11/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T09CM03069 New Garage 4133 N Stone Av Electrical Plans denied for following: 1. Change Note 1 to reflect " Electrical plans to comply with NEC 2005 and Ammendments." 2. Provide one line diagram of service feeding this new panel and identify it. 3.Provide the existing load on service feeding this new panel, and add new total for garage panel for a combined total. 4.New panel at garage is required to be grounded per NEC 250, show on plan. 5. Size feeder from existing service to new panel. 6. Provide fixture cut sheets on all fixtures. RAY T MAJUTA, EL PLAN CK 520/837/4988 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |