Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM03067
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/23/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 11/23/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the fan coils are to be attached to the building structure. Reference: Section 302.1, IMC 2006. |
| 11/23/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/23/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/23/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. ADD INTERIOR PARTITION DETAIL INDICATING BRACING OF TOP OF WALL TO EXISTING STRUCTURE. GIVE SIZE OF BRACE AND SPACING, CONNECTION OF BRACE TO EXISTING STRUCTURE AND TO TOP OF NEW WALL. 2. PROVIDE EITHER HIGH/LOW DRINKING FOUNTAIN, OR SINGLE POINT OF USE DISPENSER. |
| 11/23/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/23/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a drinking fountain or a point of use water dispenser. 2. Show how the water temperature at the lavatories is to be kept below 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. |
| 11/23/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/23/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/23/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/23/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 11/24/2009 | CPIERCE1 | WWM | REVIEW | Needs Review |