Permit Number: T09CM03067
Parcel: 12208015A

Address:
4122 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03067
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2009 TERRY STEVENS ZONING REVIEW Approved
11/23/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the fan coils are to be attached to the building structure. Reference: Section 302.1, IMC 2006.
11/23/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2009 ROBERT SHERRY WATER REVIEW Approved
11/23/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ADD INTERIOR PARTITION DETAIL INDICATING BRACING OF TOP OF WALL TO EXISTING STRUCTURE. GIVE SIZE OF BRACE AND SPACING, CONNECTION OF BRACE TO EXISTING STRUCTURE AND TO TOP OF NEW WALL.
2. PROVIDE EITHER HIGH/LOW DRINKING FOUNTAIN, OR SINGLE POINT OF USE DISPENSER.
11/23/2009 JASON GREEN ENGINEERING REVIEW Approved
11/23/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a drinking fountain or a point of use water dispenser.
2. Show how the water temperature at the lavatories is to be kept below 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
11/23/2009 DAVE MANN FIRE REVIEW Approved
11/23/2009 ERIC NEWCOMB ADA REVIEW Passed
11/23/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/23/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/24/2009 CPIERCE1 WWM REVIEW Needs Review