| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2009 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/04/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 12/04/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/21/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/21/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved. Removing the ceiling provides the required height but how can the 22" diameter water heater be removed from a closet that is 3'-9" x 2'-0" when the platform is 2'-0" x 2'-0" leaving only a 24"x 21" opening for the water heater to pass through? Clarify how the proposed water heater, along with the required piping, valves, recirculation pump, expansion tank, electrical disconnect, and mop sink are to be located in (and removable from) a closet that is only 3'-9" x 2'-0". Reference: Section 103.2.3, UPC 2006. |
| 12/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. An office space is identified by ASHRAE 62.1-2004 as having low contaminant concentration, low sensory-irritation intensity and inoffensive odor (Section 5.17.1 and Table 6-1). In addition, your calculations show less than one person being in each exam room. A more appropriate category for a dental exam room as shown in Table 6-1 may be a "Pharmacy (prep. area)". Provide justification for the use of the ventilation rate for "office space" for exam rooms having medical gas service. Reference: Sections 106.3.1 and 403.3, IMC 2006 and Section 6.1.1 and footnote 6, Table 6-1, ASHRAE Standard 62.1-2004. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/23/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 12/23/2009 | SUE REEVES | REJECT SHELF | Completed |