Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM03066
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the north arrows for the plumbing and dental plans to agree with the actual orientation of the building (see the mechanical drawings for the correct orientation). Reference: Section 103.2.3, UPC 2006. 2. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. 3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 4. Provide a design for the mounting of the shelf for the water heater to the building structure along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 5. Clarify how the proposed water heater, along with the required piping, valves, recirculation pump, expansion tank, electrical disconnect, and mop sink are to be located in (and removable from) a closet that is only 3'-9" x 2'-0" with an 8'-0" ceiling. Reference: Section 103.2.3, UPC 2006. 6. Clarify the nature of the compressed air and vacuum "outlets provided per dental plan". Reference: Section 103.2.3, UPC 2006. 7. Provide the size and material of the intake pipe for the air compressor. Reference: Section 103.2.3, UPC 2006. 8. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (e.g. drain from P-6). Reference: Section 707.4, UPC 2006. Note that the cleanout note in Section 15400 on sheet MP-1 is correct for the IPC but not for the UPC. 9. The lower detail 2/P2, Medical Gas Manifold Detail, refers to a zone valve detail; where is the referenced detail? Reference: Section 103.2.3, UPC 2006. 10. Provide specifications and details to show how the fire-rating will be preserved at the piping penetrations of the fire-resistance-rated partitions. Reference: Section 1502.0, UPC 2006. |
| 11/30/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Provide the size of the water meter serving the proposed 35 GPM demand. |
| 12/02/2009 | DSANTAC2 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/03/2009 | GBONILL1 | WWM | REVIEW | Approved | |
| 12/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Reprint sheet M1 so that the notes at the top of the page can be read. Reference: Section 106.3.1, IMC 2006. 2. With regard to the medical gas closet, revise the note calling for the upper louver to be located "at 6" below ceiling or truss". The ceiling is called out as 8'-0" AFF but the bottoms of the roof trusses are located at 10'-8" AFF in the area of the medical gas closet. Reference: Section 3006.2.1, IFC 2006. 3. Show how the 20-minute, self-closing door to the medical gas room complies with the requirements of Section 3006.2.1, IFC 2006: "Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1-hour." 4. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 5. Provide listing information for the proposed clothes dryer to show that the proposed 3-1/2" x 6" dryer exhaust duct is sized correctly. Reference: Sections 304.1 and 504.6, IMC 2006. 6. Provide justification for the use of the ventilation rate for "office space" for exam rooms having medical gas service. Reference: Sections 106.3.1 and 403.3, IMC 2006 and Section 6.1.1 and footnote 6, Table 6-1, ASHRAE Standard 62.1-2004. |