Permit Number: T09CM03047
Parcel: 12807280A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM03047
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2009 DAVE MANN FIRE REVIEW Approved
12/10/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/14/2009 DSANTAC2 ELECTRICAL-COMMERCIAL REVIEW Approved
12/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the specifications for the chiller; how does an air-cooled chiller accommodate evaporative cooling water? Reference: Section 106.3.1, IMC 2006.
2. Provide information to show that the proposed chiller complies with the efficiency requirements of Section 503.2.3, IECC 2006. According to the manufacturer, Airstack water chillers scheduled for operation below 40 degrees Fahrenheit require anti-freeze in the chilled water. If so, provide information regarding the anti-freeze solution to be employed, and its effect on the chiller efficiency.
3. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006.
12/23/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved