Review Details: COMMERCIAL TI

Permit Number - T09CM03030
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2009 TERRY STEVENS ZONING REVIEW Approved
11/18/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
11/18/2009 ROBERT SHERRY WATER REVIEW Approved
11/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/18/2009 JASON GREEN ENGINEERING REVIEW Approved
11/18/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Complete the design for the water heater support. Specify how the brackets are to be mounted to the wall. Provide the dimentions for the brackets. Reference: Sections 106.3.1 and 302.1, IMC 2006.
11/18/2009 MARTIN BROWN FIRE REVIEW Approved
11/18/2009 ERIC NEWCOMB ADA REVIEW Passed
11/18/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/18/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/19/2009 DROBEY1 WWM REVIEW Needs Review