Permit Number: T09CM03022
Parcel: 126050320

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM03022
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
11/18/2009 MARTIN BROWN FIRE REVIEW Approved
11/24/2009 GERRY KOZIOL WWM REVIEW Approved
11/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0; OCCUPANCY LOAD: THERE ARE INCONSISTENCIES IN THE OCCUPANCY CLASSIFICATIONS AND THE OCCUPANCY LOAD. IN THE OCCUPANCY CLASSIFICATION, YOU INDICATE 360 SF OF S-1 OCCUPANCY, AND 1765 SF OF B OCCUPANCY. IN THE OCCUPANCY LOAD CALCULATION, YOU INDICATE AN E OCCUPANCY FOR 954 SF, AND B OCCUPANCY FOR 1171 SF. VERIFY IF WE ARE S-1/B OCCUPANCY CLASSIFICATION, OR E/B CLASSIFICATION. CHANGE THE OCCUPANCY LOAD AS REQUIRED.
2. SHEET A0; OCCUPANCY CLASSIFICATION: IF THIS IS A S-1/B OCCUPANCY CLASSIFICATION, THERE IS NO REQUIRED SEPARATION BETWEEN THOSE AREAS PER THE 2006 IBC TABLE 508.3.3. HOWEVER, IF YOU ARE CALLING THESE AN E/B CLASSIFICATION, A 2 HOUR SEPARATION WALL IS REQUIRED PER THE IBC TABLE. THIS DIRECTLY AFFECTS NOTE 1 OF THESE REVIEW COMMENTS. CLARIFY.
3. SHEET A1; FLOOR PLAN: THE DOORS INTO THE MEN'S AND WOMEN'S RESTROOMS NEED TO MEET THE REQUIREMENTS OF ICC/ANSI A117.1-2003, SECTION 404.2.3 AND FIGURE 404.2.3.1(a) FOR MANEUVERING CLEARANCES AT DOORS. PROVIDE A DIMENSION ON THE FLOOR PLAN INDICATING THE REQUIRED 18" DIMENSION IS MET.
4. SHEET A3; HEADER SCHEDULE: THE HEADER DETAIL INDICATES BEARING ON WOOD STUDS, WHILE THE PLAN INDICATES MASONRY WALLS. ARE THERE ANY NEW WOOD HEADERS ON THIS PROJECT, OR SHOULD ALL NEW HEADERS REFERENCE DETAIL 2/A3? CLARIFY.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/02/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
12/04/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/15/2009 ROBERT SHERRY WATER REVIEW Approved
12/15/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide a drain for the watertight pan under the water heater to an approved location. Reference: Section 508.4, UPC 2006.
3. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
12/15/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural details to show how the fan coils are being connected to the building structure. Reference: Section 302.1, IMC 2006.
2. The building occupancy analysis on sheet A0 is unclear. If the occupancy is actually S1/B/E, a 2-hour fire separation will be required between the S1 and E/B occupancy, affecting the duct penetration of the garage. Resolve with the architect and modify as required.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2010 SUE REEVES APPROVAL SHELF Completed
01/07/2010 GERARDO BONILLA OUT TO CUSTOMER Completed