Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM03006
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/01/2009 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Plans denied for the following: 1. Have 800 amp rated SES being fed with 800 amp main and 70 amp breaker fro PV system. This is a code violation of 2005 NEC 690.64(B)(2). Confirmed rating of SES with Electrical contractor, Amonte electric. This would be a code compliant installation under 2008 NEC but would need to file appeal with Building Official. 2. Change rating of SES on sheets E4 and E5 from 1600 amp to 800 amp. Rich Jiroudek Electric Plns Examining 520-954-0161 |