Permit Number: T09CM03006
Parcel: 14026037B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM03006
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Plans denied for the following:

1. Have 800 amp rated SES being fed with 800 amp main and 70 amp breaker fro PV system. This is a code violation of 2005 NEC 690.64(B)(2). Confirmed rating of SES with Electrical contractor, Amonte electric. This would be a code compliant installation under 2008 NEC but would need to file appeal with Building Official.

2. Change rating of SES on sheets E4 and E5 from 1600 amp to 800 amp.

Rich Jiroudek
Electric Plns Examining
520-954-0161