Permit Number: T09CM03006
Parcel: 14026037B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM03006
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 2646 E Commerce Center, T09CM03006
21 KW Photovoltaic System


The electrical plans have been denied for the following:

1.Sheet E-1 of 2 shows 4 fixtures on circuit L1-41, then Sheet E-2 of 2 shows the lighting for PKG Canopy on circuit L1-22 and circuit 41 as spare ?
2.Provide information that shows compliance with City of Tucson/Pima County Outdoor Lighting Ord 10135. Are new fixtures full-cut off ?

Ray T Majuta
DPDS, Elect Pln Ck
City of Tucson
11/19/09
Ray.Majuta@tucsonaz.gov
11/20/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved