Permit Number: T09CM03003
Parcel: 116240980

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM03003
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2009 GERRY KOZIOL WWM REVIEW Denied NEED 5TH FLOOR CREDIT EVALUATION
12/14/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-16-09
Activity: T09CM03003
Address: 1345 W Clausen Circle
Applicant: Parker Schier

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. As of 6/12/2007 the City of Tucson has adopted the 2006 IRC. All plan pages/notes should reference this code. Appeal to the Building Official for use of 2003 IRC.

SITE PLAN:
3. Verify square footage calculations, R106.1.1.

FLOOR PLANS:
4. Specify safety glazing on window schedule for windows 1, 5, 6 (within 24" of doorways) R308.4.
5. Specify nonabsorbent wall surface minimum 6' above the floor with fiber-cement board backing in tub/shower enclosures, R307.2, R702.4.2.

SECTIONS - DETAILS:
6. Provide accurate cross-references to details on section views, R106.1.1.

PLUMBING PLAN:
7. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.
8. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.

MECHANICAL PLAN:
9. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.

ELECTRICAL PLAN:
10. Show locations of smoke detectors (hallways/areas leading to sleeping rooms), R313.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
12/21/2009 SUE REEVES REJECT SHELF Completed