Permit Number: T09CM02995
Parcel: 12405007B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 825 E University Bl, T09CM02995
Yogurt Shop

The electrical pland have been denied for the following:
1. Circuit A-22 is in the panel schedule , cannot find on the plan.
2. Item 9 last review asked for the load provided with this space in addition with the existing load on the 1200 amp service in order to detremine that this new load is adquately handeled by the service.
3. Item 11 last review asked for the cut sheet for the Yogut machines because of the two different loads used.
4. Item 13 on last review asked for compliance with current outdoor lighting code ,the plans do not show any type of coverage which would allow for the fixture lumen to be excluded for the current request.
5. A-31 in the panel schedule is used for the office and lobby, the new use is for the dine area lights?
6. A-7 on the panel schedule is used for the existing freezer, and on the plan for track lighting?

Ray T Majuta
Electrical Plan ck
PDSD< City of Tucson
12/21/09