12/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: T09CM02995
825 E UNIVERSITY BL
YOGURT SHOP

The electrical plans have been denied for the following;

1. Coffee Maker on power plan shows circuit A 26,28,30, the panel schedule shows it on circuit A 12,14.
2. The Point of Sale recept on power plan is also shown on A 12 ?
3. On the power plan the Pannini circuit is shownon A 1, also shows a tie to A 3,5 also circuit B 31 is tied to the same ciecuit, explain ?
4. B 33 is to a receptacle on plan, it is also on part of a yogurt machine .
5. A 16 on plan is alone, part of coffee brewer in panel schedule?
6. Exhaust fan on plan is showing circuit A 37,39,41, in the panel schedule Panel C is shown ?
7. A 34 on plan is shown to cooler, however it is for a dipping cabinet ?
Had to stop review,the power plan does not coincide with the panel schedule.
8. Panel C on one line diagram shows a 70 amp breaker,on the panel it shows a 60 amp breaker.
9. Provide the total load now being put on the whole service in addition to this load.
10. Provide 2006 IECC Lighting Load Calculations required with TI submittals.
11.Panel load calculations incorrect,some yogurt machine loads differ, should be the same or verirfy by machine cut sheets.
12. NEC 2005 210-8 requires commercial kitchens to have all receptacles protected by GFI.
13.Show compliance with City of Tucson Outdoor Lighting Ord # 10135 for any lighting installed outdoors.

Ray T Majuta
Elec Pln Ck,City of Tuc PDSD
12/17/09
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2009 THAUSER1 OUT TO CUSTOMER Completed
12/18/2009 SUE REEVES REJECT SHELF Completed