Permit Number: T09CM02995
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/13/2009 ERIC NEWCOMB ADA REVIEW Passed
11/13/2009 ROBERT SHERRY WATER REVIEW Approved
11/13/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Directly-connected appliances not equipped with an air gap or internal backflow protection shall have an apprpriate backflow protection device installed.
2. Clarify which appliances have indirect wastes.
3. Provide cleanouts for all sinks that have horizontal waste piping.
4. Revise the riser diagram near the ice cream dipping area to match the plumbing plan.
5. Verify the total developed length for the gas piping system.
6. Provide the listing information for the non-vented gas burner and show how the products of combustion will be removed from the space.
7. Substitution of PEX for copper will require supplemental sizing calculations, i.e. a revision to the plans.
11/13/2009 ERIC NEWCOMB ZONING HC REVIEW Passed
12/15/2009 CPIERCE1 WWM REVIEW Needs Review
12/15/2009 CPIERCE1 ZONING REVIEW Needs Review
12/15/2009 CPIERCE1 ENGINEERING REVIEW Needs Review
12/15/2009 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/15/2009 CPIERCE1 FIRE REVIEW Needs Review