Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02962
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02962
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2009 TERRY STEVENS ZONING REVIEW Approved
11/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Approval of the plans by the Pima County Health Department is required prior to approval from the City of Tucson.
2. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 401.1, UPC 2006.
3. Coordinate the plumbing design with the architectural design: the prep sink is a hand sink according to the architect and the mop sink is new. Reference: Section 103.2.3, UPC 2006.
4. Provide a floor drain in the scullery area. Reference: Sections 411.2.2 and 704.3, UPC 2006.
5. Appliances (e.g. ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
6. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0 and 801.2.3, UPC 2006.
7. Provide a direct waste connection for the hand sink Reference: Sections 304.0 and 801.2.3, UPC 2006.
11/09/2009 ROBERT SHERRY WATER REVIEW Approved
11/09/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/09/2009 JASON GREEN ENGINEERING REVIEW Approved
11/09/2009 RONALD BROWN ZONING HC REVIEW Approved
11/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/10/2009 MARTIN BROWN FIRE REVIEW Approved
11/13/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2009 SUE REEVES APPROVAL SHELF Completed
11/23/2009 SUE REEVES OUT TO CUSTOMER Completed