Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02946
Parcel: 10512020C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02946
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated property
11/16/2009 DAVE MANN FIRE REVIEW Approved
11/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.0; CODE ANALYSIS: ADD ICC/ANSI A117.1-2003 TO THE LIST FOR ACCESSIBILITY.
2. SHEET A0.2; TOILET ACCESSORIES DETAIL: PLACE THE PAPER DISPENSER PER ANSI FIGURE 604.7.
3. SHEET S4.4; DETAIL 4(b): THE DETAIL REFERENCES A SOILS REPORT. IF ONE EXISTS, PROVIDE FOR REVIEW. IF ONE DOES NOT EXIST, REMOVE NOTE.
4. GENERAL: 3/32" MINIMUM LETTERING HEIGHT IS REQUIRED ON ALL DRAWINGS. REVISE SHEETS S1.1, S1.2, S1.3, AND S1.4.
5. GENERAL: DID NOT LOCATE IN THE GENERAL STRUCTURAL NOTES ON THE DRAWINGS THE ALLOWABLE SOIL BEARING VALUE USED. PROVIDE IN NOTES (CALCULATIONS INDICATE 1000 PSF).
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/19/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
11/19/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/24/2009 GERRY KOZIOL WWM REVIEW Approved
12/07/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
3. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
12/07/2009 ROBERT SHERRY WATER REVIEW Approved
12/07/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the size of the condensate drain system per Section 307.2.2, IMC 2006, as amended by the City of Tucson. (When two or more units are tied together, the minimum drain size shall be 1".).
2. Provide calculations demonstrating adequate ventilation based on the requirements of Section 403, IMC 2006.
3. Materials exposed in plenums shall conform to Section 602.2.1, IMC 2006.
4. Provide smoke detectors in the return air ducts of the rooftop units, upstream of any filters, exhaust air connections, or outside air connections. Reference: Sections 606.1 and 606.2, IMC 2006.
12/11/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T09CM02946
Building Plan (1st Review)

TRANSMITTAL DATE: December 11, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan.. Please submit two copies of the approved and stamped site plan with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm02946.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
12/11/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Denied Plans denied for the following:

1. Provide disconnecting means on plans within sight of scissor lift, produce cooler, and automatic door opener.
NEC 430.102(B) and 440.14

2. Provide disconnecting means on plans for cooler door and freezer door heaters per NEC 422.31(B).

3. Provide on plans ratings of all disconnecting means. Indicate if disconnects to be fused or unfused, and if fused include size of fusing.

4. If scissor lift controller does not have integral disconnect then need to provide disconnecting means for controller.
NEC 430.102(A)

Rich Jiroudek
Electric plans examining
520-954-0161

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
01/27/2010 SUE REEVES REJECT SHELF Completed