Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02922
Parcel: 117121280

Review Status: Completed

Review Details: OTHER

Permit Number - T09CM02922
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a design for the grease exhaust duct, i.e. duct sizes, fire wrap, geometry.
2. Provide structural calculations and show how the hood is to be supported from the building structure.
3. Show where the roof-top units are located and show that they can be safely supported by the roof structure.
4. Show that the grease exhaust fan will automatically start when cooking commences.
5. Specify the equipment that is proposed for this activity; e.g. mechanical and electrical characteristics.
6. Show the balancing information on the drawings.
11/10/2009 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review
11/10/2009 SREEVES1 FIRE REVIEW Needs Review
11/10/2009 SREEVES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2009 SUE REEVES OUT TO CUSTOMER Completed