Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM02922
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the grease exhaust duct, i.e. duct sizes, fire wrap, geometry. 2. Provide structural calculations and show how the hood is to be supported from the building structure. 3. Show where the roof-top units are located and show that they can be safely supported by the roof structure. 4. Show that the grease exhaust fan will automatically start when cooking commences. 5. Specify the equipment that is proposed for this activity; e.g. mechanical and electrical characteristics. 6. Show the balancing information on the drawings. |
11/10/2009 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
11/10/2009 | SREEVES1 | FIRE | REVIEW | Needs Review | |
11/10/2009 | SREEVES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/10/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |