Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T09CM02922
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a design for the grease exhaust duct, i.e. duct sizes, fire wrap, geometry. 2. Provide structural calculations and show how the hood is to be supported from the building structure. 3. Show where the roof-top units are located and show that they can be safely supported by the roof structure. 4. Show that the grease exhaust fan will automatically start when cooking commences. 5. Specify the equipment that is proposed for this activity; e.g. mechanical and electrical characteristics. 6. Show the balancing information on the drawings. |
| 11/10/2009 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/10/2009 | SREEVES1 | FIRE | REVIEW | Needs Review | |
| 11/10/2009 | SREEVES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/10/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |