Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a design for the grease exhaust duct, i.e. duct sizes, fire wrap, geometry.
2. Provide structural calculations and show how the hood is to be supported from the building structure.
3. Show where the roof-top units are located and show that they can be safely supported by the roof structure.
4. Show that the grease exhaust fan will automatically start when cooking commences.
5. Specify the equipment that is proposed for this activity; e.g. mechanical and electrical characteristics.
6. Show the balancing information on the drawings.
11/10/2009 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review
11/10/2009 SREEVES1 FIRE REVIEW Needs Review
11/10/2009 SREEVES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review