Permit Number: T09CM02919
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02919
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide performance specifications and operating weight for RTAC-7.
2. Provide structural calculations and diagrams for the installation of RTAC-7.
12/09/2009 ERIC NEWCOMB ADA REVIEW Passed
12/09/2009 ROBERT SHERRY WATER REVIEW Approved
12/09/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/09/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/09/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/11/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/11/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
12/11/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2009 MARTIN BROWN FIRE REVIEW Approved