Permit Number: T09CM02918
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02918
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/09/2009 ROBERT SHERRY WATER REVIEW Approved
12/09/2009 ERIC NEWCOMB ADA REVIEW Passed
12/09/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/09/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide protection of the trap seal for the proposed floor drain. A trap guard has not been approved for use in the City of Tucson. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
2. Revise the water and the waste and vent riser diagrams to show the new work.
12/09/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/11/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/11/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
12/11/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2009 MARTIN BROWN FIRE REVIEW Approved
12/21/2009 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
12/21/2009 GERRY KOZIOL WWM REVIEW Approved