Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02914
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/03/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/03/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/03/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
11/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/03/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
11/03/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/03/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
11/03/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/03/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/06/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |