Permit Number: T09CM02899
Parcel: 14026045A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02899
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2009 TERRY STEVENS ZONING REVIEW Approved
11/02/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/02/2009 ERIC NEWCOMB ADA REVIEW Passed
11/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET IA1.0: PROVIDE ENLARGED PLAN OF ACCESSIBLE RESTROOMS, ALONG WITH WALL ELEVATIONS INDICATING CRITICAL DIMENSIONS PER ANSI FIGURE 604.5.1.
2. SHEET M-1: PROVIDE STRUCTURAL ANALYSIS FOR FOR ADDITIONAL ROOF LOADS ON EXISTING STRUCTURAL MEMBERS.
11/02/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
11/02/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Provide mounting details for the units. Reference: Section 302.1, IMC 2006.
11/03/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/03/2009 ROBERT SHERRY WATER REVIEW Approved
11/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how water is to be supplied to the proposed evaporative coolers.
11/03/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
11/17/2009 DROBEY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2009 DELMA ROBEY OUT TO CUSTOMER Completed