Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02899
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 11/02/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 11/02/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/02/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET IA1.0: PROVIDE ENLARGED PLAN OF ACCESSIBLE RESTROOMS, ALONG WITH WALL ELEVATIONS INDICATING CRITICAL DIMENSIONS PER ANSI FIGURE 604.5.1. 2. SHEET M-1: PROVIDE STRUCTURAL ANALYSIS FOR FOR ADDITIONAL ROOF LOADS ON EXISTING STRUCTURAL MEMBERS. |
| 11/02/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 11/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 11/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Provide mounting details for the units. Reference: Section 302.1, IMC 2006. |
| 11/03/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/03/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how water is to be supplied to the proposed evaporative coolers. |
| 11/03/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 11/17/2009 | DROBEY1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |