Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02888
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/30/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006. |
| 10/30/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project 2106 W Grant Rd, T09cm02888 Comply with Mechinacil to interlock ex-fan to unit providing air to restroom, or install a TC. Ray T Majuta Elect Pln Ck 10/30/09 |
| 10/30/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/30/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET M-1: PROVIDE CALCULATIONS FOR EXISTING ROOF FRAMING WHERE NEW 750 POUND HEAT PUMP IS LOCATED. |
| 10/30/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/30/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/30/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/30/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/30/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/30/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/30/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved |