Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02888
Parcel: 10321342A

Address:
2106 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02888
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
10/30/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference: Section 403.2.1, IMC 2006.
10/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project 2106 W Grant Rd, T09cm02888

Comply with Mechinacil to interlock ex-fan to unit providing air to restroom, or install a TC.

Ray T Majuta
Elect Pln Ck
10/30/09
10/30/2009 ROBERT SHERRY WATER REVIEW Approved
10/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET M-1: PROVIDE CALCULATIONS FOR EXISTING ROOF FRAMING WHERE NEW 750 POUND HEAT PUMP IS LOCATED.
10/30/2009 GERRY KOZIOL WWM REVIEW Approved
10/30/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/30/2009 JASON GREEN ENGINEERING REVIEW Approved
10/30/2009 MARTIN BROWN FIRE REVIEW Approved
10/30/2009 ERIC NEWCOMB ADA REVIEW Passed
10/30/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/30/2009 ERIC NEWCOMB ZONING HC REVIEW Approved