Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02864
Parcel: 133073400

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09CM02864
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2009 DAVE MANN FIRE REVIEW Denied Fire Comments

1. The site plan for this project was approved only on the condition the buildings would have fire sprinklers.

2. The IRC cannot be used this project.
11/13/2009 GERRY KOZIOL WWM REVIEW Passed
11/17/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T09CM02864

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007; the 2006 UPC with amendments on 7/10/2007; effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation. All new SFR and duplex plans should reference these codes. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

SITE PLAN:

1. Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1.

FOUNDATION PLANS:

1. Locate and specify all anchor-bolt size and spacing on Detail 3/3. Maximum spacing 6' o/c and within 12" of each sill plate end, R403.1.6.
2. Show Alternate Braced Wall Panel device location and installation method for providing the required 1800 LBS uplift capacity, R602.10.6.

FLOOR PLANS:

1. Locate and identify brace wall panels at the ends (within 12.5') of the enclosed exterior wall line with 25' OC spacing for avoiding an engineered design with shear panels, Table R602.10.6.
2. Identify ceiling heights in all areas on floor plan, R602.10.5. Note average height at sloped ceiling areas. The required braced wall panel width increases as the height increases per Table R602.10.6.
3. Show the location of a minimum 22" x 30" attic access. Attic access is required if the space exceeds 30 SQ FT with a minimum of 30" of headroom, and shall be located in a hallway or readily accessible space, R807.1.

SECTIONS - DETAILS:

1. Show the ceiling gypsum board as either 5/8" or ½" sag resistant when applied to 24" o/c ceiling framing, IRC table R702.3.5 footnote d.
2. Specify the minimum thickness of structural sheathing at Detail 3/3, R602.10.3.
3. Specify veneer anchoring method, weepholes, water-resistive barrier and support (ties spaced max 24" o/c horizontally & vertically and supporting max of 2.67 SQ FT), R703.2 & R703.7.
4. Show 1" air space between sheathing and veneer R703.7.4.2.
5. Provide an attic space ventilation calculation for any enclosed attic space and specify size and location of all vents needed to comply, R806.2.
6. Show compliance with R806.4 by stating "no vapor retarders at the ceiling" for roof areas without vented attic space.

PLUMBING PLANS:

1. Provide protection of (indoor rated) equipment (water heater) located outdoors, or exterior rated enclosure, UPC 508.27.
2. Note the requirement for the new 1" gas branch line connected to the gas meter (35' developed length), or provide a gas line diagram showing all pipe sizes, lengths and connected loads between the point of connection and the gas meter. UPC 1217.2 & Table 12-8. Existing gas pipes may require upgrading.

MECHANICAL PLANS:

1. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Show the smoke alarm required on the outside of the sleeping area, R313.2.
2. Provide a panel schedule the general description for the Furnace Air Handler, Living Room and Storage receptacles, E3304.11 & E3606.2.
3. Show the Furnace on a separate branch circuit. Appliances and equipment on general purpose circuits may not exceed 50% of the branch circuit rating, E3602.5.
4. Note that combination type arc-fault circuit interrupter shall protect bedroom outlets including receptacles, lights and smoke detectors, E3802.12.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations.
2. Provide spec sheets for all full cut-off fixtures showing the lamp type, placement and fixture wattage. All other fixtures are assumed to be unshielded (non-FCO style). Fixtures are only exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the "U" factors of the windows and doors on the plans, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
11/24/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1; SITE PLAN: PER THE 2006 IBC SECTION 1106.6, ACCESSIBLE PARKING SPACES SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE BUILDING ENTRANCE. THIS WOULD INDICATE AN ACCESSIBLE PARKING SPACE NEARER TO THE BUILDING AND WITH A MORE DIRECT ROUTE.
2. SHEET 1; SITE PLAN: PROVIDE SPOT ELEVATIONS ON THE SITE PLAN TO INDICATE THE ACCESSIBLE PARKING SPACE AND ACCESS AISLE MEET THE SLOPE REQUIREMENTS OF ICC/ANSI A117.1-2003, SECTION 502.5.
3. SHEET 1; SITE PLAN: PROVIDE SPOT ELEVATIONS ON THE SITE PLAN TO INDICATE THE ACCESSIBLE ROUTE FROM THE PARKING LOT TO THE BUILDING MEET THE SLOPE REQUIREMENTS OF ANSI SECTION 402.2.
4. SHEET 1; SITE PLAN: THE ACCESSIBLE PARKING SPACE MUST BE 132" (12') WIDE FOR VAN PARKING PER IBC SECTION 1106.5 AND ANSI SECTION 502.2.
5. SHEET 2; GENERAL NOTES (2): EXPAND NOTE 2 ON FIREBLOCKING TO INCLUDE AREAS LISTED IN THE IBC SECTION 717, AND SPECIFY FIREBLOCKING MATERIAL.
6. SHEET 2; FLOOR PLAN: PER THE IBC SECTION 1107.6, THIS NEW UNIT MUST BE FULLY ACCESSIBLE.
7. SHEET 2; FLOOR PLAN: DOORWAYS SHALL HAVE A CLEAR OPENING WIDTH OF 32" PER ANSI SECTION SECTION 404.2.2. VERIFY ALL DOORWAYS MEET THIS CRITERIA.
8. SHEET 2; FLOOR PLAN: CHANGES IN THE FLOOR LEVEL FROM THE PORCH INTO THE LIVING AREA MUST MEET ANSI SECTION 303 REQUIREMENTS.
9. SHEET 2; FLOOR PLAN: THE ENTRY DOOR AT THE NORTHEAST CORNER INDICATES IT SWINGS INTO THE ROOM AND OUT OF THE ROOM. VERIFY. ANSI FIGURE 404.2.3.1(a) REQUIREMENTS MUST BE MET.
10. SHEET 2; GENERAL PLAN NOTES: THIS PROJECT FALLS UNDER THE 2006 IBC. REVISE NOTES AS REQUIRED.
11. SHEET 2; FLOOR PLAN: THE BATHROOM MUST BE FULLY ACCESSIBLE. PROVIDE AN ENLARGED PLAN ON THE DRAWINGS, INDICATING DIMENSIONS PER ANSI SECTION 604. INCLUDE WALL ELEVATIONS OF THE BATHROOM, INDICATING GRAB BARS, PAPER DISPENSERS, AND THEIR LOCATIONS.
12. SHEET 2; FLOOR PLAN: DINING AND WORK SURFACES IN THE DINING ROOM MUST MEET ANSI SECTION 902 REQUIREMENTS. PROVIDE WALL ELEVATIONS ON THE DRAWINGS.
13. GENERAL: PER THE IBC SECTION 903.2.7, AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED.
14. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/30/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
12/04/2009 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 19324 N. Corte El Rancho
T09CM02864
Convert residence to Bed & Breakfast
Residential Building Plan (1st Review)

TRANSMITTAL DATE: December 4, 2009

1. Zoning will not be able to approve this site plan until the Special Exception for the use has been approved. Once approved on the plan provides; Special Exception number, Date of Approval, Any Conditions of Approval. Additional comments may be forth coming once the conditions of approval are provided.

2. Clearly indicate the accessible route from both the parking area and from the street. Provide the max. cross slope (2%) and max. running slope (5%) for the sidewalk leading to the residence. This route must meet the requirements of D.S. 2-08.5.1.

3. Provide a fully dimensioned vehicle use area (parking and parking area access lane).

4. The vehicle use area must meet the requirements of LUC Section 3.3.7.3, indicate on the plan how the vehicle use area complies.

5. Per D.S. 2-09.0.4.1 Proximity to Main Entrances. Class 2 bicycle parking facilities will be located no more that 50 feet from the main building entrance. This said provide a dimension from the proposed bicycle parking to the main entrance.

6. Per D.S. 2-09.0.4.4 Class 2 bicycle parking facilities will be clearly visible from the adjacent sidewalks, drives and the main entrance.

7. Provide a Class 2 bicycle parking detail that meets the requirements of D.S. 2-08.5.0

8. Depending on how the above comments are addressed additional comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm0864.doc