Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02862
Parcel: 11518100A

Address:
1201 N MAIN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02862
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2: WHERE IN THE 2006 IBC TABLE 2902.1 DO YOU FIND THAT NO DRINKING FOUNTAIN IS REQUIRED? TABLE LISTS 1 DRINKING FOUNTAIN (HIGH/LOW OR SINGLE POINT-OF-USE PER IBC SECTION 1109.5) FOR UP TO 1000 OCCUPANTS. VERIFY.
2. PREVIOUS COMMENT 4: THE NOTE FOR THE VERTICAL GRAB BAR HAS BEEN ADDED TO SHEET A2 PER YOUR RESPONSE. PLEASE INDICATE THE VERTICAL GRAB BAR ON SHEET PE.
3. PREVIOUS COMMENT 5: DID NOT FIND THE PAPER DISPENSER LOCATION ON SHEET A2 PER YOUR RESPONSE. INDICATE THE LOCATION ON SHEET PE.
4. GENERAL: PROVIDE TWO COMPLETE SETS OF DRAWINGS (INCLUDING THE REVISED SHEETS AS REPLACEMENTS FOR THE ORIGINAL SHEETS) FOR THE NEXT REVIEW.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/03/2009 LOREN MAKUS ENGINEERING REVIEW Approved
12/04/2009 DAVID RIVERA ZONING REVIEW Denied DSD TRANSMITTAL

FROM: David Rivera
Principal Planner

PROJECT: T09CM02862
1201 N. Main Avenue
Building Plan Review
Commercial Storage Use

TRANSMITTAL DATE: December 4, 2009

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Zoning has reviewed the building plan for compliance with the site plan. As of this review date the site plan has not been approved by all PDSD plan reviewers so technically the building plan cannot be approved by zoning at this time.

2. While it appears that the building complies with all zoning requirements the building plans reviewers have denied the plans and therefore the changes requested could trigger some modifications to the plans and zoning must review the plans once more to ensure that the any possible changes do not affect zoning compliance. Zoning will review the building plans and compare to the site plan once again to ensure compliance.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plans.
12/08/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/08/2009 RICHARD JIROUDEK ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2009 DELMA ROBEY OUT TO CUSTOMER Completed