Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T09CM02862
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1: PROVIDE PROJECT DATA INFORMATION ON THIS SHEET, INCLUDING RELEVANT CODES AND REGULATIONS, EXIT REQUIREMENTS, MEANS OF EGRESS, AND OCCUPANCY REQUIREMENTS FOR THE NEW SPACE. 2. SHEET A2: PROVIDE DRINKING FOUNTAIN AND SERVICE SINK ANALYSIS PER IBC TABLE 2902.1. 3. SHEET A2; FLOOR PLAN (DOOR SCHEDULE): PROVIDE LIST OF DOOR HARDWARE ON SCHEDULE PER IBC SECTION 1008.1.8. 4. SHEET PE; ELEVATION 1: ADD VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. 5. SHEET PE; ELEVATION 1: LOCATE THE PAPER DISPENSER PER ANSI A117.1, FIGURE 604.7. 6. SHEET S1; FOUNDATION NOTES: IS THERE A SOILS REPORT FOR THIS PROJECT? NOTE 1 INDICATES THERE IS, WHILE NOTE 3 INDICATES THERE IS NOT (BUT ASSUMED VALUES MUST BE VERIFIED BY A QUALIFIED SOILS ENGINEER). CLARIFY. 7. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS. |
| 10/30/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 11/03/2009 | RICK MYERS | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a site utility plan, to include, but not limited to, yardwater piping - size and location, material type, RPPBP size and location. 4" sewer and BCS location, to include material type and any other information that may be helpful. 2. Include water heater detail. Provide expansion tank, vacuum relief valve, T&P relief drain, and pan drain piping and termination. 3. Include a Fixture Schedule, for lavatory and trim, and water closet and accessories. |
| 11/05/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/10/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 1201 N Main St T09CM02862 New Storage Building The Electrical plans have been denied for the following: 1. The City of Tucson requires throughCommercial Submittal Requirements to provide The new plus the existing load to the service in amps. 2. Outdoor Lighting Calculations per The 2005 City of Tucson/Pima County Outdoor Lighting Ord 10135, for outside lighting. 3. Provide Fixture schedule, on the types being used. 4. Provide 2006 IECC Budget Lighting Calculations as required by City Of Tucson Commercial Submittal Requirements. Ray Majuta Elect Pln CK City of Tucson PDSD 11/15/09 Ray.Majuta@tucsonaz.gov |
| 11/16/2009 | DAVID RIVERA | ZONING | REVIEW | Denied | The building plans cannot be approved until the zoning site plan comments have been addressed and the site plan is approved. Some of the zoning comments are related to height and setbacks which need to be addressed before the building plans can be reviewed for complinace with setbacks |
| 11/19/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | The site plan must be approved before the building plan can be approved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/20/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |