Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02848
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/05/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/05/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/05/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 11/05/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 11/05/2009 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 11/05/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/05/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/06/2009 | DAVE MANN | FIRE | REVIEW | Approved |