Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02837
Parcel: 12709012E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02837
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the termination of the condensate drain for FC-1. Reference: Section 807.2,
UPC 2006.
2. Comment not addressed. Clarify how detail 103 relates to FC-1. Reference: Section 106.3.1, IMC 2006
12/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. See sheet P-1, keynote number 2. Reference 807.2 2006 UPC ... the condensate connection
shall be located in the area controlled by the same person controlling the air conditioned space.
2. Comment not resolved. See sheet P-2 Fixture Specifications, P-2A. Include manufacturers specifications and listings for all fixtures. Reference 301.1 2006 UPC
4. Comment not addressed. Include how the domestic water is to be sterilized. Reference 609.9 2006
UPC.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2009 DELMA ROBEY OUT TO CUSTOMER Completed