Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02837
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/20/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/20/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the termination of the condensate drain for FC-1. Reference: Section 807.2, UPC 2006. 2. Comment not addressed. Clarify how detail 103 relates to FC-1. Reference: Section 106.3.1, IMC 2006 |
12/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. See sheet P-1, keynote number 2. Reference 807.2 2006 UPC ... the condensate connection shall be located in the area controlled by the same person controlling the air conditioned space. 2. Comment not resolved. See sheet P-2 Fixture Specifications, P-2A. Include manufacturers specifications and listings for all fixtures. Reference 301.1 2006 UPC 4. Comment not addressed. Include how the domestic water is to be sterilized. Reference 609.9 2006 UPC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/10/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |