Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02837
Parcel: 12709012E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02837
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2009 MARTIN BROWN FIRE REVIEW Approved
10/28/2009 GERRY KOZIOL WWM REVIEW Approved
10/30/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/30/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/02/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. See sheet P-1, keynote number 2. Reference 807.2 2006 UPC ... the condensate connection shall be located in the area controlled by the same person controlling the air conditioned space. 2. See sheet P-2 detail 204. This detail is not used on this project. 3. See sheet P-2 Fixture Specifications. Include manufacturers specifications and listings for all fixtures. Reference 301.1 2006 UPC 4. See sheet P-1. The Health Room has a floor sink, and the Break Room has a floor drain. Both break room sinks are to be directly connected to the sanitary sewer. Show how the sinks are to be connected, and how the indirect waste receptors are connected to the sanitary sewer. Provide an isometric drawing showing these connections. 5. Include how the domestic water is to be sterilized. Reference 609.9 2006 UPC.
11/02/2009 RMYERS1 WATER REVIEW Approved
11/09/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the termination of the condensate drain for FC-1. Reference: Section 807.2, UPC 2006.
2. Clarify how detail 103 relates to FC-1. Reference: Section 106.3.1, IMC 2006
11/18/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2009 SUE REEVES OUT TO CUSTOMER Completed
11/20/2009 SUE REEVES REJECT SHELF Completed