Permit Number: T09CM02829
Parcel: 10703178A

Review Status: Completed

Review Details: SITE

Permit Number - T09CM02829
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2009 MARTIN BROWN FIRE REVIEW Denied Please indicate existing fire hydrant location(s), with dimensions to buildings and/or property lines. Refer to City of Tucson amendments to the 2006 International Fire Code (section 508) for spacing and location requirements.
11/03/2009 RBROWN1 ADA REVIEW Passed Not a COT owned/operated property
11/09/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: November 9, 2009
SUBJECT: 2525 N Jackrabbit Ave- Engineering Review
TO: George Lance
LOCATION: T13S R13E Sec34 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM02829 (Site Plan), T09BU01581 (Grading Plan), and T09OT02314 (Floodplain Use Permit)


SUMMARY: Engineering Division of Planning Development Services Department has received and reviewed the proposed site plan (T09CM02829), grading plan (T09BU01581), Floodplain Use Permit (T09OT02314) and Drainage Report (JE Fuller Hydrology and Geomorphology, Inc., 06NOV09) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading plan at this time. The following items need to be addressed:


DRAINAGE REPORT COMMENTS:

1) DS Sec.10-02.2.3.1.4.C.8: Revise the Drainage Exhibit and grading plan attachment in the Report to clearly label and delineate the existing FEMA 100-year AE floodplain associated with the Silvercroft Wash (as shown on page 10 of the EL Rio Medio attachment). The FEMA 100-year floodplain across the site must be labeled and referenced on both the drainage exhibits and on the proposed site/grading plan sheets.


SITE PLAN COMMENTS:

2) DS Sec.2-02.2.1.A.2: Clarify the existing lot area calculation provided on Sheet A1, proposed at 0.35 acres. The north lot has a total area of 0.4 acres and the southern lot has a total area of 0.33 acres. If combining the lots the total area of lot coverage would be 0.73 acres not the 0.35 shown.

3) DS Sec.2-02.2.1.A.5: Clarify the proposed lot lines as shown on the site plan. Per the last recorded Assessor map the property is 2 separate parcels and per the site plan there are proposed improvements crossing the property boundaries, clarify. Verify if the Zoning Section will require a lot combination prior to site plan approval for any proposed improvements offsite (2525 N Jackrabbit Ave).

4) DS Sec.2-02.2.1.A.8: Revise the back-up spur provided at the end of the PAAL located on the west side of the existing building and proposed vehicular use area on the proposed site plan to label the minimum 3-foot radii.

5) DS Sec.2-02.2.1.A.10: Revise the site plan (plan view or legend) to provide the dimension for both the near (185 feet with 20-foot stem) and far (110 feet with 20-foot stem) side of the sight visibility triangles for the PAAL entrance per DS Sec.3-01.5.3.

6) DS Sec.2-02.2.1.A.11: Verify and label the 18-feet radii for both sides of the proposed driveway per City of Tucson Transportation Access Management Guidelines (TAMG), Section 5.5. Refer to DS Sec.3-01.3.2.C for street development standards. Standard driveway entrance designs (Standard Detail for Public Improvement #206, Keynote #11) or reduced radii for curb returns will require prior approval, in writing, from TDOT Permits and Codes, Thad Harvison at 837-6592. Verify that both the site plan sheets and civil sheets match. Currently Keynote #11 on the site plan sheet calls out a standard entrance however plan view shows constructed radii. The plan must represent what is proposed.

7) DS Sec.2-02.2.1.A.12: Clarify the sidewalk dimension on the site plan, Sheet A1, and the grading plan, Sheet C1, for the proposed sidewalk adjacent to the building and PAAL. A 5-foot pedestrian access width for the sidewalk adjacent to the PAAL is required. The civil sheets and Keynote call out 5-feet however the site plan view calls out 6-feet, clarify.

8) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ANSI Standard requirements that apply to this project.

9) DS Sec.2-02.2.1.A.15: Revise all sheets to label and delineate the regulatory 100-year floodplain limits for the Silvercroft Wash on site. The FEMA SFHA Zone AE floodplain must be labeled and dimensioned in plan view along with water surface elevations that were used to determine finished floor elevations.

10) DS Sec.2-02.2.1.A.16: Revise the site plan and grading plan sheets to label and dimension the ponding limits within the vehicular use area per the Drainage Report.

11) DS Sec.2-02.2.1.A.16: Provide number, detail, spacing and location for all proposed wall openings that meet the minimum requirements of the Drainage Report. The proposed wall will be constructed and permitted under a separate permit however; number of openings, wall vent (basin weir) sizing and spacing is required to be shown on the site plan to verify minimum requirements of the Drainage Report.

12) DS Sec2-02.2.1.A.16: Revise Keynote #3 on the site plan to state; "Water Harvesting Areas to be depressed a minimum of 6-inches." Refer to the City of Tucson Water Harvesting Guidance Manual, Ordinance # 10210 for recommendation on how to construct and maintain the required water harvesting areas for onsite flow containment.

13) DS Sec2-02.2.1.A.16: Revise the site plan and grading plan sheets to correctly label and dimension the required retention basin along the west property line. Per Keynote #8 on both the site plan and grading plan this area is proposed as granite groundcover and does not correctly label or dimension the required basin per the Report, revise

14) DS Sec2-02.2.1.A.19: Revise the site plan to clearly label the center lines of Jackrabbit Ave.

15) DS Sec.2-02.2.1.A.19: Revise the site plan to label and dimension the existing right-of-way for Jackrabbit Ave.

16) DS Sec.2-02.2.1.A.21: Provide dimensions from the street monument lines to the existing curb, driveway and utility lines.

17) DS Sec.2-02.2.1.A.32: Revise the site plan, Keynotes and Detail 1/C2 to provide the minimum dimensions and construction details for the required refuse containers. Refer to DS Sec.6-01 (Figures 1, 2 and 3) for all required refuse enclosure dimensions and construction details. Refer to the draft Development Standards at:
http://www.tucsonaz.gov/dsd/DS_6-01_Environmental_Services_12-16-08.pdf

18) DS Sec.2-02.2.1.A.32: Verify the maneuverability, label and dimension the required 36-foot and 50-foot radii for the refuse container; clearly label these in plan view. Provide the required 14-foot by 40-foot clear approach and verify the maximum allowed back up distance for maneuverability. Refer to DS Sec.6-01 for all refuse requirements. The refuse vehicle can not back-up into the future lot and parking area covered with 2 shot chip seal, if this area is proposed to be used for maneuverability then the area must be constructed to DS Sec.3-05 and 6-01 surfacing requirements.

19) Review and approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction. Refer to the following links for TDOT Forms and applications:

a) http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/applications.html /

b) http://www.dot.ci.tucson.az.us/engineering/pia.php

c) Or contact Thad Harvison at 837-6592 for all additional questions regarding r-o-w.

20) Be advised that further comments may be forth coming on resubmittal of the site plan.


GRADING PLAN:

21) Provide a copy of the stamped approved site plan (T09CM02829). The grading plan can not be approved until verification that all details, locations, dimensions, and plan profiles match the approved site plan. Verify all information associated with the site plan is shown on the grading plan which will be used as the construction document.

22) Revise General Note #3 to provide the basis of bearing used to establish dimensions and bearings of property lines and property corners. The basis of bearing should be established from 2 found, physically monumented points described and shown on the site plan.

23) Provide a note on the grading plan sheet to label the total acreage of the lot(s) and the disturbed acreage as proposed. The north lot has a total area of 0.4 acres and the southern lot has a total area of 0.33 acres. If combining the lots the total area of lot coverage would be 0.73 acres not the 0.35 shown, revise.

24) DS Sec.11-01.4.1.C: Provide typical lot grading details, show minimum side and rear setbacks. Provide detailed cross sections for each perimeter, fully labeled and dimensioned to verify the required 2-foot setback from property boundaries.

25) DS Sec.11-01.4.1.C.4: Provide a detail for the location and type of drainage structure, label and dimension all scuppers that are used for collecting roof drainage and discharges at the pedestrian sidewalk. The scuppers proposed under the sidewalk must be designed and constructed to convey the 10-year flood flow. Provide a drainage statement showing scupper calculations that demonstrate that the 10-year flood flow is contained under the sidewalk.

26) Revise the site plan and grading plan sheets to label and dimension the ponding limits within the vehicular use area per the Drainage Report.

27) Revise all sheets to label and delineate the regulatory 100-year floodplain limits for the Silvercroft Wash on site. The FEMA SFHA Zone AE floodplain must be labeled and dimensioned in plan view along with water surface elevations that were used to determine finished floor elevations.

28) Provide number, detail, spacing and location for all proposed wall openings that meet the minimum requirements of the Drainage Report. The proposed wall will be constructed and permitted under a separate permit however; number of openings, wall vent (basin weir) sizing and spacing is required to be shown on the grading plan to verify minimum requirements of the Drainage Report.

29) Revise Section 16/C2 for the proposed basin to label and dimension the basin size per the Drainage Report. Per the Report the basin has an overall width of 9 feet however per the plan set and section the basin is proposed to be constructed at 3 feet wide, revise. Verify that all dimensions, slopes, details, location, sizing, etc for all drainage improvements meet the minimum requirements of the Drainage Report.

30) Verify how the stormwater from the vehicular use area drains into the proposed retention basin. Per Section 3/C2 the area adjacent to the basin is proposed as extruded curb, clarify how stormwater drains into the basin over or around the proposed curbing. Verify that all detail, sections and plan view clearly show how this area is to be constructed to drain stormwater into the detention basin.

31) Revise Section 14/C2 to label the 2 shot chip seal proposed on the southern lot. Per the Section this area is to remain natural, however per plan view the entire area is to be covered with 2 shot chip seal.

32) Revise the site plan and grading plan sheet to label the minimum finished floor elevation in plan view for the future building. The pad elevation and future FFE is required to be shown in plan view since the proposed improvements are within a FEMA SFHA Zone AE 100-year floodplain.

33) Verify and label the 18-feet radii for both sides of the proposed driveway per City of Tucson Transportation Access Management Guidelines (TAMG), Section 5.5. Refer to DS Sec.3-01.3.2.C for street development standards. Standard driveway entrance designs (Standard Detail for Public Improvement #206, Keynote #11) or reduced radii for curb returns will require prior approval, in writing, from TDOT Permits and Codes, Thad Harvison at 837-6592. Verify that both the site plan sheets and civil sheets match. Currently Keynote #11 on the grading plan sheet calls out a standard entrance however plan view shows constructed radii. The plan must represent what is proposed.

34) Clarify grading note "h" on the grading plan sheet. Since the site is less than an acre a SWPPP is not required, the note should state: "Call for a Pre-construction meeting prior to start of earthwork. To schedule a PDSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Planning Development Services Department, or contact PDSD Engineering at 791-5550 extension 2101, or schedule inspections online at:
http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html

35) Please ensure that the grading plan is consistent with the site plan and Drainage Report. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf.


FLOODPLAIN USE PERMIT COMMENTS:

36) The Floodplain Use Permit (FUP) will be conditioned and issued concurrently with the grading plan application and stamped approved plan set. All conditions related to the FUP will be based on the grading plan review.


GENERAL COMMENTS:

Please provide a revised site plan, grading plan, and Drainage Report that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the site plan and grading plan review.

For questions, or to schedule an appointment, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
Planning Development Services
11/12/2009 ANDREW CONNOR NPPO REVIEW Approved
11/12/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. A 6' wall is required along entire street frontages for loading zone per LUC Table 3.7.2-I. Identify screening element on the site and landscape plan.

2. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.

3. Landscape plans shall incorporate water-conserving designs. A water-conserving design includes grouping of plants with similar water requirements and use of efficient irrigation systems per LUC 3.7.4.1 Nandina Domestica & Myoprum Parvaflorium are both a moderate water user and will need to be watered throughout their life span. Desert Spoon, Texas Ranger, and Chilean Mesquite requires little to no supplemental watering when established and will be affected negatively by over irrigating Salvia leucantha (shrub) & Euphorbia rigida (ground-cover) would be acceptable substitutions.

4. Storm water detention/retention basins shall be landscaped to enhance the natural configuration of the basin. Plants located in the bottom one-third (1/3) of the detention/retention basin must be adaptable to periods of submersion. Design criteria are set forth in Development Standard 10-01.0.

5. Add the following notes to the landscape plan replacing General Note # 9:


DS 2-06.6.0 MAINTENANCE STANDARDS.

a. Any plant material in areas of required landscaping that does not survive will be replaced with an equivalent size and species within thirty (30) days.

b. Plant material will be pruned as necessary to control size but not to disrupt the natural growth pattern or characteristic form of the plant except as necessary to achieve height clearance for visibility and pedestrian passage or to achieve a continuous opaque hedge if required.

c. Clipping and pruning of the plant material are required to allow maximum shading while preserving surveillance opportunities and preventing obstructive overhang into walks, curb areas, drives, and line of sight triangles. For general guidelines on height clearance of tree canopies, refer to Sec. 2-06.3.6.D, Sec. 2-06.3.6.E, Sec. 2-06.3.6.F, and Sec. 2-06.3.7.D.

d. All dead or removed plant material will be replaced with plant material acceptable under the requirements of the xeriscape landscaping regulations. Replacement material will be a minimum fifteen (15) gallon size for trees and five (5) gallon size for shrubs.

e. Regular landscape maintenance should ensure water efficiency and include, but not be limited to, pruning, mulching, weeding, and litter removal.


6. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

7. Additional comments may apply.
11/30/2009 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T09CM02829
2525 N. Jackrabbit Ave.
Site Plan


TRANSMITTAL DATE: 12/01/09

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.A.5 This site contains two (2) separate parcels therefore you will need to show how the parcels can work as stand alone parcels if sold separately or provide a Pima County Tax Parcel Combo and a recorded covenant regarding development and use of real property. Provide recording docket and page information for the covenant on the site plan.

Remove lot dimensions and bearing from property line between parcels.

2. DS 2-02.2.1.A.6 Provide on the site plan the dimensions of the foot print of the existing building.

3. DS 2-02.2.1.A.8 Clearly indicate whether a van accessible handicap parking space is being provided.

4. DS 2-02.2.1.A.9 Please provide a plan view detail of the proposed class 2 bicycle parking spaces. Single rack spaces placed in a row will allow a minimum of seventy -two (72) inch length per bicycle parking space and a minimum of thirty (30) inches between outer spaces of racks. A five (5) foot wide access aisle measured from the front or rear of the seventy-two (72) inch long parking space will be provided beside each row. Lighting will be provided such that all facilities are thoroughly illuminated and visible from adjacent sidewalks, parking lots, or buildings, during working hours. The surface of the facility can be surfaced the same as for motor vehicle parking or with a minimum of one (1) inch thickness of one-fourth (1/4) inch aggregate material.

The detail 7-C2 of the class two bicycle rack does not meet the requirements of DS 2-09. Minimum 2 point support. Revise detail.

The bicycle parking calculations are to be based on the number of vehicle parking spaces provide not on the number required. Revise.

Class one bicycle parking spaces can be substituted with class two when less than 50 parking spaces are provided, class one bicycle parking spaces are not required nor do they appear to be provided. Revise calculations. If they are to be provided, a detail of the class one bicycle locker and location of the space is required to be provided on the site plan.

5. DS 2-02.2.1.A.11 Clearly indicate the location of all curbing that will prevent vehicles from driving onto unimproved portions of the site.

6. DS 2-02.2.1.A.13 If applicable, indicate the locations and types of proposed signs (wall, freestanding, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Also indicate if there are existing billboards on site. Billboards will be required to meet all LUC requirements as stated in LUC Sec. 3.5.4.26. If none exists please state so.

7. DS 2-02.2.1.A.25 If applicable, provide the location and type of any existing or proposed site lighting.

8. DS 2-02.2.1.A.31 Provide the subject to sections for the proposed use. Should read as follows: General Manufacturing "34", subject to: Sec. 3.5.5.1.B, .F, .G, and .H

Per subject to section 3.5.5.1.H outdoor storage is not allowed in the street perimeter yard setback. Provide a note on the plans clearly indicating such.

9. DS 2-02.2.2.A.1 The gross area of the lot must include both lots after the combination. Revise.

This will affect the FAR calculations. Revise.

The FAR calculations should be provided for the existing building only not for the future building.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T09CM02829.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
12/01/2009 RONALD BROWN ZONING HC REVIEW Denied SHEET A1
1. At the accessible parking space:
a. The arrows and direction notes are wrong, please fix.
b. The area on the south side of the accessible parking space is presumed to be the aisle. Please dimension, provide markings and insure slope is as per ICC (ANSI) 117.1, section 502.5. Show on large scale detail.
2.The ramped landing shown on the South side of the building is for what? It directs visually impaired persons to the PAAL without a marked crossing and no end to where they are directed to go. Please delete unless you have a fully functional marked crossing.
3. At the pedestrian public right of way connection at Jackrabbit Av., note 2 calls for a tactile warning strip as per detail D/A1 which shows detectable warning strips. A detectable warning strip is not required here. Please delete the note reference.
4. At note 10: replace the ADA reference with a reference to ICC (ANSI) 117.1 and correct referenced detail D/C1 to D/A1.
5. Detail Nos. C/A1 and 9/C2 are redundant. Also generic plan details are not acceptable. Please provide a large scale detail that reflects exactly the same design shown on the site plan and reference only one such detail.
SHEET C2
6. At detail 15, truncated domes are not required on the flared sides of the ramp. Please remove note reference requiring detectable warnings on the flared sides.

END OF REVIEW
12/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location of the main water lines and fire hydrants
b. the rim elevation of the upstream manhole.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2009 CINDY AGUILAR OUT TO CUSTOMER Completed