Permit Number: T09CM02827
Parcel: 11307198B

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T09CM02827
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2010 STEVE SHIELDS ZONING REVIEW Approved
12/10/2009 RONALD BROWN ZONING HC REVIEW Approved
12/14/2009 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/14/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/15/2009 DAVE MANN FIRE REVIEW Approved
12/15/2009 ANDREW CONNOR NPPO REVIEW Approved
12/17/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: December 17, 2009
SUBJECT: 3 Single Family Residences
TO: SEPASSI REZA & MALEKNIAZI NAHID CP/RS
5216 N STANDING ROCK PL
TUCSON AZ 85750-7029
TO: a.s.i architects studio inc.
LOCATION: 1447 E Blacklidge Drive, T13S, R14E, Section 31, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09CM02827 (Second Review)


RESUBMITTAL REQUIRED: Site Plan, Grading Plan and Drainage Report

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Site Plan, Grading Plan and Drainage Report.

Site Plan:

1. The most recent aerial photo of the building does not match what is depicted on the site plan. Please modify site plan to represent actual footprint of existing buildings and/or clarify. Show existing buildings on site plan. Add note in regards to whether or not the existing buildings are to remain or to be demolished. Add activity number to site plan of any demolition permits.
Response: Provide activity number for demolition referenced in 2008 on the plans.
2. Complied
3. Complied
4. Complied
5. Complied
6. Complied
7. Complied
8. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
Response: There is floodplain that should be identified along Blacklidge Dr.
9. Complied
10. Complied
11. Complied
12. Complied
13. Verify that all easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
Response: Standard note to remain until plans are approved. Acknowledge that there are no easements on parcel.
14. Provide City Field Book and page number for benchmark per D.S. 2-02.2.1.23. Provide contour interval on plan, preferably with north arrow and scale.
15. Verify that all fences, walls, or vegetation for screening and sight visibility have been indicated by type, material, height, location and spacing per D.S. 2-02.2.1.27.
Response: Show 2' setback between wall and property line.
16. Show site plan and grading plan number in the lower right hand corner of each sheet accordingly per D.S. 2-02.2.1.29.
Response: Show the site plan number and grading plan number on all sheets.
17. DS Sec.2-02.2.1.A.32: the detail with dimensions for refuse container on the site plan indicated that there will be curbside pick up. Enclosures are required to have a minimum inside clear dimension of 10 feet by 10 feet between steel bollards that are required between the container and the enclosure's rear and sidewalk. Refer to DS Sec.6-01.4.2 for specifications and requirements on access, placement of containers, bin enclosure and construction. For curbside pickup a letter of approval will be required from COT Environmental Services and a Development Standard Modification Request (DSMR) may be required prior to site plan approval.
Response: Comments to remain. DSMR(s) required.
18. DS Sec.2-02.2.1.A.32: Label and show the maneuverability for refuse vehicles in plan view at the proposed refuse container location. Current positioning of trash area does not allow for 14' X 40' clear approach, show access dimensioning to proposed trash enclosure.
Response: Comments to remain. DSMR(s) required.
19. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Please indicate off site elevation within 100' of property line.
Response: Show offsite elevations within 100' of property lines.
20. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
Response: Standard comment is to remain until plans are approved.
21. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
Response: Show roof drainage along with flow arrows.
22. Complied
23. Complied
24. Complied
25. Complied
26. Please clarify the purpose of site plan key note 9.
Response: Clarify on site plan or in key note 9.
27. Complied
28. Call out peak discharges entering and exiting the site.
Response: Provided Q100(s) are not representative of information provided in drainage report.
29. Complied
30. Black markings within identified curb should be called out. Are these depressed curbs?
Response: Unable to locate note identifying depressed curb.
31. Provide proof that water will continue north onto public street north of northern adjacent parcel. Must show that there is no adverse impact.
Response: The drainage report indicated 5.31 cfs for developed conditions. The report appears to be the old version with old design exiting onto west property. Please revise and update accordingly.
32. Additional comments may be forthcoming.

Drainage Report:

**Schedule meeting with Engineer and Architect and City of Tucson staff. **
1. Backwater analysis shows elevations in the range of 2707 and site/grading plans indicate 70 elevations. Please review and revise accordingly.
2. Provide floodplain limits and water surface elevations from drainage report on site/grading plan.
3. Drainage Report is not reflective of site plan and grading plan.
4. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
02/09/2010 SUE REEVES REJECT SHELF Completed