Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T09CM02822
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02822
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
10/22/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Indicate the intended use of this space (e.g. beauty salon, hobby shop, etc.) and show that there is adequate ventilation for the intended use. Reference: Section 403.3, IMC 2006.
10/22/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2009 ROBERT SHERRY WATER REVIEW Approved
10/22/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/22/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
10/22/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A combination waste and vent system may not be used for sinks roughed in above the floor.
2. Show how scalding will be prevented at the sinks.
3. Provide a shut off valve before the water heater.
4. Provide listing information for the proposed sinks.
10/22/2009 DAVE MANN FIRE REVIEW Approved
10/22/2009 ERIC NEWCOMB ADA REVIEW Passed
10/22/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/22/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
10/29/2009 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/29/2009 DELMA ROBEY OUT TO CUSTOMER Completed