Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02822
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Indicate the intended use of this space (e.g. beauty salon, hobby shop, etc.) and show that there is adequate ventilation for the intended use. Reference: Section 403.3, IMC 2006. |
10/22/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/22/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/22/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/22/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
10/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. A combination waste and vent system may not be used for sinks roughed in above the floor. 2. Show how scalding will be prevented at the sinks. 3. Provide a shut off valve before the water heater. 4. Provide listing information for the proposed sinks. |
10/22/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
10/22/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
10/22/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/22/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
10/29/2009 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/29/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |