Permit Number: T09CM02801
Parcel: 13809007E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02801
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
10/20/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide confirmation from a structural engineer that the roof is capable of supporting the proposed condensing unit.
2. The minimum lettering size is 3/32".
10/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2009 ROBERT SHERRY WATER REVIEW Approved
10/20/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/20/2009 GERRY KOZIOL WWM REVIEW Approved
10/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a floor drain in each rest room. Reference: Section 411.2, UPC 2006.
2. Water-free urinals are not Code-compliant fixtures per the UPC. Submit an appeal to the Building Official requesting approval to utilize a water-free urinal based on the International Plumbing Code. Reference: Sections 211.0 (insanitary), 301.2, 405.2, 409.0, 601.1, and 1005.0, UPC 2006.
10/20/2009 PAUL MACHADO ENGINEERING REVIEW Approved
10/20/2009 DAVE MANN FIRE REVIEW Approved
10/20/2009 RONALD BROWN ADA REVIEW Passed
10/20/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/20/2009 RONALD BROWN ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2009 SUE REEVES OUT TO CUSTOMER Completed