Permit Number: T09CM02800
Parcel: 121060070

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02800
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/18/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. All plumbing fixtures (e.g. vegetable sink) and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
2. Provide an indirect waste connection for the vegetable sink. Reference: Section 801.2.3, UPC 2006.