Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09CM02800
Parcel: 121060070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02800
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the structural calculations to show point loading for the hood and include the weight of a person working on the hood. Provide details to show how the Type I hood is supported from the building structure. Reference: Section 507.6, IMC 2006.
2. Provide a non-combusible, non-absorbant, cleanable surface (e.g. stainless steel sheet) to the walls adjoining the Type I hood and extending 18" beyond the hood. Reference: Section 507.9, IMC 2006.
3. Comment not addressed. Clarify the design of the Type I hood, i.e. "fully compensating" with regard to the proportion of any air being supplied to the hood cavity. Reference: Sections 507.13 and 508.2, IMC 2006.
4. Comment not resolved; tell the contractor how to comply with the requirement. Provide information to show that the operation of the hood exhaust system complies with the requirements of Section 507.2.1.1, IMC 2006.
5. Comment not addressed; tell the contractor how to comply with the requirement. Show how the introduction of make up air into the space complies with Section 508.1.1, IMC 2006.
6. Comment not resolved; see sheet M2. The minimum size of the lettering shall be 3/32" in height.
7. Detail 1/M1 shows flex duct connected to the air plenum on the hood. Make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006.
8. Show how the clearance reduction noted in detail 1/M1 complies with the requirements of Section 308, IMC 2006.
01/22/2010 DROBEY1 WWM REVIEW Needs Review
01/22/2010 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/22/2010 DROBEY1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/10/2009 RONALD BROWN ADA REVIEW Passed
12/10/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/10/2009 RONALD BROWN ZONING HC REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2010 DELMA ROBEY OUT TO CUSTOMER Completed