Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02800
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the structural calculations to show point loading for the hood and include the weight of a person working on the hood. Provide details to show how the Type I hood is supported from the building structure. Reference: Section 507.6, IMC 2006. 2. Provide a non-combusible, non-absorbant, cleanable surface (e.g. stainless steel sheet) to the walls adjoining the Type I hood and extending 18" beyond the hood. Reference: Section 507.9, IMC 2006. 3. Comment not addressed. Clarify the design of the Type I hood, i.e. "fully compensating" with regard to the proportion of any air being supplied to the hood cavity. Reference: Sections 507.13 and 508.2, IMC 2006. 4. Comment not resolved; tell the contractor how to comply with the requirement. Provide information to show that the operation of the hood exhaust system complies with the requirements of Section 507.2.1.1, IMC 2006. 5. Comment not addressed; tell the contractor how to comply with the requirement. Show how the introduction of make up air into the space complies with Section 508.1.1, IMC 2006. 6. Comment not resolved; see sheet M2. The minimum size of the lettering shall be 3/32" in height. 7. Detail 1/M1 shows flex duct connected to the air plenum on the hood. Make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006. 8. Show how the clearance reduction noted in detail 1/M1 complies with the requirements of Section 308, IMC 2006. |
| 01/22/2010 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 01/22/2010 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/22/2010 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 12/10/2009 | RONALD BROWN | ADA | REVIEW | Passed | |
| 12/10/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/10/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/10/2009 | RONALD BROWN | ZONING HC | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |