Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02784
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/16/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/22/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | See work flow sheet,RTMajuta,10/22/09 |
| 10/22/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The minimum exhaust rate for the restroom is 75 CFM per water closet. |
| 10/22/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE ELEVATION OF EAST WALL OF TOILET. SHOW LOCATIONS OF GRAB BAR AND PAPER DISPENSER. PROVIDE WALL SURFACE PER IBC 1210.2. 2. PROVIDE DETAIL FOR PARTITION WALLS MEETING THE REQUIREMENTS OF IBC 1607.13, INDICATING BRACING OF TOP OF WALL TO EXISTING STRUCTURE, INCLUDING CONNECTOR SIZES, SPACING. |
| 10/22/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the size and location of the exiting water meter on the plans along with the size and location of the reduced pressure backflow preventer. |
| 10/22/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | An appeal to the building official is required prior to reviewing the drawings to the International Plumbing Code. |
| 10/22/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/22/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/22/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 11/06/2009 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 11/06/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/06/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |