Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2010 GBONILL1 WWM REVIEW Needs Review
10/16/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
10/16/2009 PAUL MACHADO ENGINEERING REVIEW Approved
10/16/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a mechanical design for the new refrigeration equipment.
2. Provide balancing information for the two exhaust grilles shown in detail 101 and a means for balancing.
3. Provide a list of the hazardous materials being stored in the exhausted area and the amounts being stored.
10/16/2009 ERIC NEWCOMB ADA REVIEW Passed
10/16/2009 ROBERT SHERRY WATER REVIEW Approved
10/16/2009 STEVE SHIELDS ZONING REVIEW Approved
10/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/16/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. RACKS OVER 12 FEET IN HEIGHT REQUIRE STRUCTURAL CALCULATIONS FOR RACK DESIGN AND CONNECTION AT FLOOR.
10/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T09CM02777
6874 S Palo Verde
TI Warehouse.


Electrical Plans ok however need information on condensing units which need to be provided on the Mechanical Plans, see mechanical requesr.

Ray T Majut
Elect PLan CK
PDSD City of Tucson
10/16/09
Ray.Majuta@tucsonaz.gov
10/19/2009 DAVE MANN FIRE REVIEW Denied Fire Comments

Panic hardware is required for both exits from the H occupancy. IFC 1008.1.9

A separate permit is required for the fire sprinklers.