Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02777
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 10/16/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 10/16/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/16/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/16/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical design for the new refrigeration equipment. 2. Provide balancing information for the two exhaust grilles shown in detail 101 and a means for balancing. 3. Provide a list of the hazardous materials being stored in the exhausted area and the amounts being stored. |
| 10/16/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/16/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/16/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 10/16/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/16/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. RACKS OVER 12 FEET IN HEIGHT REQUIRE STRUCTURAL CALCULATIONS FOR RACK DESIGN AND CONNECTION AT FLOOR. |
| 10/16/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T09CM02777 6874 S Palo Verde TI Warehouse. Electrical Plans ok however need information on condensing units which need to be provided on the Mechanical Plans, see mechanical requesr. Ray T Majut Elect PLan CK PDSD City of Tucson 10/16/09 Ray.Majuta@tucsonaz.gov |
| 10/19/2009 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments Panic hardware is required for both exits from the H occupancy. IFC 1008.1.9 A separate permit is required for the fire sprinklers. |