Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02757
Parcel: 128121810

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T09CM02757
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2010 RONALD BROWN BUILDING-RESIDENTIAL REVIEW Denied GENERAL:
1. There are several sheets in this submittal package that have lettering smaller than the required 3/32" height. Please reconfigure all fonts to be no less than 3/32" in height, (upper and lower case) and resubmit.
2. Please provide consecutive sheet numbers on each construction drawing, R106.1.1.
FLOOR PLANS:
3. Identify ceiling heights in all areas. Note average height at sloped ceiling areas, R305.1.
4. Show the location of attic access min. 22"x30", R807.
5. Show fireplace location, hearth size and materials, R1001 or R1004. Provide fireplace cut sheets or note the requirement for deferred submittal approval prior to installation. Show the flue on the elevations.
6. Tub/shower enclosures require nonabsorbent wall surface min. 6’ above the floor and fiber-cement board backing, R307.2, R702.4.2.
FOUNDATION PLANS:
7. Please provide a landing or floor surface at all exterior doors, R311.4.3.
ELEVATIONS:
8. Provide an attic space ventilation calculation and note the size and location of all attic vents needed to
comply, R806.2.
9. Chimney: min 2’ above any roof point within 10’, not less than 3’ above penetration, R1003.9. Show the fireplace flue.
SECTIONS - DETAILS:
10. Detail all over-framing connections for intersecting pitched roof assemblies. Provide a minimum opening of 2" by 30" for access and ventilation between over-framed assemblies (>30 S.F.), R807.
11. Specify wall and ceiling covering. Note: Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
ELECTRICAL PLANS:
12. Electrical work shall comply with 2006 IRC chapters 33 - 42.
13. Provide equipment rated for 22,000 AIC short circuit protection when the underground cable length is less than 45 feet, 2006 Electric Service Requirements TEP SR-510.
14. Bedroom outlets shall be arc-fault protected (receptacles, lights, and smoke detectors), E3802.12.
MECHANICAL PLANS:
15. Mechanical shall comply with 2006 IRC chapters 12 - 24.
16. Show supply and return ducts with minimum R-8 insulation, R1103.2.1.
17. Designate the location, capacity and fuel type of the heating and air conditioning equipment. Designate
the locations of each supply register, return air grill and all ductwork.
18. Provide an equipment specification list, M1302.1.
19. Show the condensate line and secondary for HVAC unit, M1411.3.
OUTDOOR LIGHTING CODE
20. Provide cut sheets for all FCO fixtures showing the angle of cutoff, light emissions and fixture
wattage. All other fixtures are assumed to be unshielded (non-FCO style).
INTERNATIONAL ENERGY CONSERVATION CODE:
21. Provide a note requiring the insulation certificate shall be posted in the electrical distribution panel
before final inspection, N1101.8.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2010 CPIERCE1 OUT TO CUSTOMER Completed
04/16/2010 SUE REEVES REJECT SHELF Completed