Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM02747
Parcel: 117143340

Address:
663 S MAIN AV

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T09CM02747
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2009 STEVE SHIELDS ZONING REVIEW Approved DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 663 S Main Avenue
T09CM02747
Residential Building Plan (1st Review)

TRANSMITTAL DATE: October 13, 2009

1. The building & site plan have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Per LUC Section 3.2.6.4, H0-3 Zoning, Development Designator "L", Perimeter Yard Indicator "BB" The required perimeter yard setback to the north, south and east property line is the height of the exterior building wall. Proposed wall height of 10'-0" requires a 10'-0" setback to the north property line, proposed setback is 1'-6". Proposed wall height of 15'-2" requires a 15'-2" setback to the north property line, proposed setback is 12'-6". Proposed wall height of 15'-9" requires a 15'-9" setback to the south property line, proposed setback is 2". Proposed wall height of 14'-0" requires a 14'-0" setback to the east property line, proposed setback is 2".

3. Per LUC Section 3.2.65.B the required setback to Main Street property line is 21'-0" measured from the back of future curb, proposed is 14'-2"

4. Historic Review is required for this project.

5. Zoning will re-review the plan on the next submittal. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09cm02747.doc
10/13/2009 SSHIELD1 NPPO REVIEW Passed
12/11/2009 LOREN MAKUS ENGINEERING REVIEW Approved
12/11/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Needs Review