Permit Number: T09CM02738
Parcel: 12308024C

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T09CM02738
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2010 BIANCA RAMIREZ ENGINEERING REVIEW Needs Review
12/15/2009 DAVE MANN FIRE REVIEW Denied Area and occupant load has increased to over 100 occupants, fire sprinklers will be required. Also, please review the swing of the exit gate from the covered patio, It appears to swing in the wrong direction. Be advised that if kitchen cooking appliances locations have, or are going to be changed, kitchen exhaust hood fire suppression system may need to be revised.
12/17/2009 RONALD BROWN ZONING HC REVIEW Denied 1. Provide a large scale detail of the accessible parking plan showing compliance with ICC (ANSI), Section 502, including slopes, signage, ramps, aisles, all dimensions required and "Van Accessible" space identification.
2. Provide an accessible route connection to the public right of way, pedestrian way.
3. Provide a continous accessible route to the required rear fire exit of the building.

END OF REVIEW
12/17/2009 STEVE SHIELDS ZONING REVIEW Denied 5DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: May's Counter Restaurant
T09CM02738
Site Plan (1st Review)

TRANSMITTAL DATE: December 17, 2009

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the entire site.

2. The footprint of the building shown on the site plan does not match the floor plan. Show all areas of proposed use, areas enclosed by railing, on the site plan.

3. D.S. 2-02.2.1.A.2 Provide a legal description on the site plan.

4. D.S. 2-02.2.1.A.3 The property address is not legible due to text over text. Also clarify what the name of the restaurant will be, May's Counter or Over Easy.

5. D.S. 2-02.2.1.A.4 Provide a location map that meets the requirement of D.S. 2-05.2.1.D on the site plan.

6. D.S. 2-02.2.1.A.5 Provide lot bearings on the site plan.

7. D.S. 2-02.2.1.A.6 All existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use are to be provided on the site plan. The footprint of the building shown on the site plan does not match the floor plan. Show all areas of proposed use, areas enclosed by railing, on the site plan.

8. D.S. 2-02.2.1.A.7 Provide perimeter yard setback dimensions from all proposed structures, covered porches, to the interior lot lines.

9. D.S. 2-02.2.1.A.7 Provide a street perimeter yard setback dimension from the proposed covered porch addition to the street. Per LUC Section 3.2.6.5.B & LUC Table 3.2.6.I, ADT of 1,000 or greater, the street perimeter yard setback dimension is measured from the back of existing curb or future curb location. As it does not appear that the curb along Speedway Blvd. is at full width show the future curb and provide the perimeter yard setback dimension.

10. D.S. 2-02.2.1.A.7 Based on the C-1 Zoning Development Designator "28", Perimeter Yard Indicator "DD", the required. perimeter yard setback from the proposed "SHED COVERING STRUCTURE OVER BEER COOLER" to the north property ling is 1-1/2 times the height of the structure. Based on a building wall height of 8'-10" the required perimeter yard setback is 12.8 feet. See LUC Section 3.2.6.3 for Perimeter Yard Measurement. A Design Development Option (DDO) will need to be processed and approved prior to approval of the site plan if the 8'-0" perimeter yard setback is to remain as shown on the site plan.

11. D.S. 2-02.2.1.A.8 Provide a fully dimensioned off-street parking layout.

12. D.S. 2-02.2.1.A.8 Provide a typical parking space detail for both a standard and accessible vehicle parking space on the site plan.

13. D.S. 2-02.2.1.A.8 Per LUC Section 3.3.7.2.A the minimum length of eighteen (18) feet is required for a vehicle parking space. The parking spaces shown along the south side of the building are only 15'-0" in length. A Board of Adjustment for Variance is required for the proposed 15'-0" vehicle parking spaces.

14. D.S. 2-02.2.1.A.9 Provide a Class 2 off-street bicycle parking detail, including materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports. The required number of bicycle parking spaces cannot be verified until the provided number of vehicle parking spaces has been clarified, see comment 33 below.

15. D.S. 2-02.2.1.A.10 Show the existing and future sight visibility triangles on the site plan.

16. D.S. 2-02.2.1.A.11 Provide width dimensions for all points of egress and ingress including parking area access lanes (PAALs).

17. D.S. 2-02.2.1.A.12 Until a fully dimensioned parking layout has been provided the requirements of this section cannot be verified, see comment 11 above.

18. D.S. 2-02.2.1.A.12 Per LUC Table 3.3.7.I the proposed 19'-0" PAAL shown south of the building does not meet the 24' width for a PAAL that accesses 90 degree parking. A Board of Adjustment for Variance is required for the proposed 19'-0" PAAL.

19. D.S. 2-02.2.1.A.12 Per D.S. 2-08.3.1 a continuous pedestrian circulation path/accessible route is required to connect the building to the pedestrian circulation along the street right-of-way (ROW).

20. D.S. 2-02.2.1.A.12 Provide a dimension for the sidewalk located along the south side of the building and the vehicle parking spaces.

21. D.S. 2-02.2.1.A.12 Provide a dimension for the sidewalk located between the accessible ramp and the southwest corner of the covered patio.

22. D.S. 2-02.2.1.A.13 If applicable show the location, type, size, and height of existing and proposed signage on the plan.

23. D.S. 2-02.2.1.A.14 Fully dimension the existing loading space and show the maneuvering area on the plan.

24. D.S. 2-02.2.1.A.14 Per LUC Section 3.4.3.4 Use of Loading Area. A loading space shall be used only for the purpose it is intended and shall not be used for the repair or dismantling of vehicles or in any other manner that would interfere with the purpose for which the space is provided, this said the loading space may not be used for access to the refuse container location.

25. D.S. 2-02.2.1.A.18 Label Speedway Blvd. as an MS&R.

26. D.S. 2-02.2.1.A.19 Dimension the right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way.

20. D.S. 2-02.2.1.A.20 If applicable all easements of record must be graphically shown on the plan together with the recording information, Docket and Page reference.

27. D.S. 2-02.2.1.A.25 If applicable show the existing and/or the proposed sight lighting on the site plan.

28. D.S. 2-02.2.1.A.28 Show the existing zoning of parcel and adjacent parcels, including those across streets and alleys.

29. D.S. 2-02.2.1.A.28 The "SITE ZONING" listed under "SITE DATA" is not correct. The zoning for this parcel is C-1.

30. D.S. 2-02.2.1.A.31 Show the existing and proposed use on the site plan. The proposed use should be listed as "FOOD SERVICE "28", SUBJECT TO: SEC. 3.5.4.6.A AND .C"

31. D.S. 2-02.2.2.A.2 The proposed beer cooler should be added to the building square footage.

32. D.S. 2-02.2.2.A.3 Provide a floor area ratio per LUC Section 3.2.11 on the site plan.

33. D.S. 2-02.2.2.A.4 The vehicle parking calculation should include all areas of use, i.e. outdoor seating and waiting area and the beer cooler.
34. D.S. 2-02.2.2.A.4 Provide a bicycle parking space calculation that includes the number required and provided.
35. D.S. 2-02.2.2.A.6 Provide an expansion calculation on the plan. The expansion includes all outdoor seating, waiting area and beer cooler.
36. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t09cm02738

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
12/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location and size of the public sanitary sewer and
d. the location, invert, and rim elevation of all manholes and cleanouts.
Reference: City of Tucson Development Standard No. 2-05.0 2.3 and Section 103.2.3, UPC 2006.
12/28/2009 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Provide correct expansion calculation.

" On sites where the gross floor area of the existing building(s) is ten thousand (10,000) square feet or less, expansions in square footage of land area, floor area, lot coverage, or vehicular use area as follows.

2. If the expansion is less than fifty (50) percent, the requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval.

3. The previous approved site / landscape plan was based on a plan from 1975, duplicate the landscape indicated on the plan dated 10/14/07 on the recently submitted document.

4. Ensure that all Zoning and Engineering comments and concerns are addressed prior to Landscape approval.

5. Additional comments may apply.
12/30/2009 ANDREW CONNOR NPPO REVIEW Approved