Permit Number: T09CM02735
Parcel: 11305155A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02735
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2009 TERRY STEVENS ZONING REVIEW Approved
10/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Connection of a pumped condensate waste shall not connect directly to any part of the drainage system. Reference: Sections 805 and 814,3, UPC 2006.
10/13/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/13/2009 ROBERT SHERRY WATER REVIEW Approved
10/13/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/13/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
10/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the type of drinking fountain with the architectural drawings. The drinking fountain specified on sheet P-3 does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
10/13/2009 DAVE MANN FIRE REVIEW Approved
10/13/2009 ERIC NEWCOMB ADA REVIEW Passed
10/13/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/13/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
10/21/2009 CPIERCE1 WWM REVIEW Needs Review