Permit Number: T09CM02692
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02692
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Walls between tenant spaces in a mall are fire partitions per Section 708.1 (3), IBC 2006. Provide a fire damper for the proposed opening in the wall (sheet M-1.0).
11/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The proposed water heater is not capable of limiting the water temperature to 110 degrees Fahrenheit and the manufacturer has also changed the specifications for the proposed model number, increasing the Wattage to 4160W.