Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02692
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 11/02/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/03/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Revise the sequence of operation for the restroom exhaust fan to prevent recirculation of the air from the restroom (i.e. the fan may not be switched with the lights). Reference: Section 403.2.1, IMC 2006. |
| 11/03/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed. Coordinate the electrical requirements for the instantaneous water heater. The specified water heater uses 120V power but the plumbing schedule calls for 208V power and the electrical plans call for 277V power. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |