Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
11/02/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/03/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Revise the sequence of operation for the restroom exhaust fan to prevent recirculation of the air from the restroom (i.e. the fan may not be switched with the lights). Reference: Section 403.2.1, IMC 2006.
11/03/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Coordinate the electrical requirements for the instantaneous water heater. The specified water heater uses 120V power but the plumbing schedule calls for 208V power and the electrical plans call for 277V power.