Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T09CM02692
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/06/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
10/06/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/07/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
10/07/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan to prevent recirculation of the air from the restroom (i.e. the fan may not be switched with the lights). Reference: Section 403.2.1, IMC 2006. |
10/07/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE OCCUPANT LOAD FOR THIS SPACE. |
10/07/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/07/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. 2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006. 3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. (See text at: http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). In addition, Accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2006, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-2003. (note that "GPF" means gallons per flush) 4. State that the temperature of the hot water supply to the public lavatory will be controlled to a maximum of 110 degrees Fahrenheit (the specified instantaneous water heater can be factory-set to 110 degrees Fahrenheit). Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 5. Coordinate the electrical requirements for the instantaneous water heater. |
10/07/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/07/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
10/07/2009 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
10/07/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/07/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |