Permit Number: T09CM02692
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM02692
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2009 TERRY STEVENS ZONING REVIEW Approved
10/06/2009 JASON GREEN ENGINEERING REVIEW Approved
10/07/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
10/07/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fan to prevent recirculation of the air from the restroom (i.e. the fan may not be switched with the lights). Reference: Section 403.2.1, IMC 2006.
10/07/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE OCCUPANT LOAD FOR THIS SPACE.
10/07/2009 ROBERT SHERRY WATER REVIEW Approved
10/07/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments.
2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. (See text at: http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp). In addition, Accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2006, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-2003. (note that "GPF" means gallons per flush)
4. State that the temperature of the hot water supply to the public lavatory will be controlled to a maximum of 110 degrees Fahrenheit (the specified instantaneous water heater can be factory-set to 110 degrees Fahrenheit). Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Coordinate the electrical requirements for the instantaneous water heater.
10/07/2009 GERRY KOZIOL WWM REVIEW Approved
10/07/2009 DAVE MANN FIRE REVIEW Approved
10/07/2009 ERIC NEWCOMB ADA REVIEW Passed
10/07/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/07/2009 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.