Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T09CM02665
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. No more than one trap shall be installed on a trap arm. Reference: Section 1001.1, UPC 2006. 2. Provide a fixture description for P-16, a disposable canister. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006. 3. Clarify the change to P-15: is it being roughed in above the floor or below the floor? Based on detail 1/P4 it apears to be a clothes washer standpipe. 4. Clarify the revisions to detail 1/P5: the clouded area does not clearly show how the fixtures are to be installed. Reference: section 103.2.3, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/03/2010 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 03/03/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |