Permit Number: T09CM02665
Parcel: 114600590

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T09CM02665
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. No more than one trap shall be installed on a trap arm. Reference: Section 1001.1, UPC 2006.
2. Provide a fixture description for P-16, a disposable canister. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.
3. Clarify the change to P-15: is it being roughed in above the floor or below the floor? Based on detail 1/P4 it apears to be a clothes washer standpipe.
4. Clarify the revisions to detail 1/P5: the clouded area does not clearly show how the fixtures are to be installed. Reference: section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2010 CINDY AGUILAR APPROVAL SHELF Completed
03/03/2010 CINDY AGUILAR OUT TO CUSTOMER Completed