11/13/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/13/2009 CPIERCE1 ZONING REVIEW Needs Review
11/13/2009 CPIERCE1 WWM REVIEW Needs Review
11/13/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
11/13/2009 MARTIN BROWN FIRE REVIEW Denied Please provide quantities and types of gases in Gas Room and how these quantities relate to the International Fire Code for maximum allowable quantities allowed .
Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
11/13/2009 ROBERT SHERRY WATER REVIEW Approved