Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T09CM02665
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/13/2009 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 11/13/2009 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 11/13/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 11/13/2009 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide quantities and types of gases in Gas Room and how these quantities relate to the International Fire Code for maximum allowable quantities allowed . Please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
| 11/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/13/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |