Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09CM02664
Parcel: 141012130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T09CM02664
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2009 MARTIN BROWN FIRE REVIEW Approved
11/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/18/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/04/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. Refer also to Section 1106.4, UPC 2006.
2. Comment not resolved. The overflow in the roof drain collector box shall have a drainage capacity equal to that of the scupper and a minimum opening height of 4". Reference: Section 1101.11.2.2.1, UPC 2006.
12/04/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; include the solar tubes in the energy calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope and be consistent with the energy calculations. The information shall, as a minimum, include the correct areas for components, U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Comment not addressed. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006.