Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T09CM02664
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/10/2009 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/18/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/18/2009 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
12/04/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. Refer also to Section 1106.4, UPC 2006. 2. Comment not resolved. The overflow in the roof drain collector box shall have a drainage capacity equal to that of the scupper and a minimum opening height of 4". Reference: Section 1101.11.2.2.1, UPC 2006. |
12/04/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; include the solar tubes in the energy calculations. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope and be consistent with the energy calculations. The information shall, as a minimum, include the correct areas for components, U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 2. Comment not addressed. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. |